The maintenance team at the Electric Power Transmission Network in the City of Karbala performed routine electrical tests on the transformer including: winding resistance measurements (WRM), transformer turns ratio (TTR), short circuit impedance (SCI), excitation current, and line-frequency power factor (a.k.a. dissipation factor or tan delta).
With the TRAX instrument, they can also perform advanced testing including: magnetic balance, Frequency Response of Stray Losses (FRSL) and OLTC Dynamic Resistance Measurement (DRM) tests.
Only the DRM test results clearly flagged a deficiency in Phase B of the OLTC, which was not observed in static measurements. Static measurements are those that are performed while the OLTC (and DETC) is stationary at each of a number of selected tap positions.
Dynamic tap changer measurements, such as provided by a DRM test, are critical to assess a resistive-type OLTC’s bridging or ‘transition’ components, which only appear in a test circuit during the OLTC’s transition from one tap position to the next. A resistive-type OLTC does not use its bridging state as a viable tap service arrangement/position, so these components never appear in the test circuit of a static measurement.